Industrial Automation

Context: MWSC apprenticeship

Status: Communication and configurations validated on tested setups

Context

This project connects PRECIA weighing equipment with a Beckhoff PLC and makes data available to Dorner Batch or RSA, depending on the receiving system. Different devices and protocols require their own mapping and decoding; they are not interchangeable without adaptation.

Objective

Make weighing data usable across equipment with different protocols and data formats.

My role

Weighing equipment configuration, communication integration and diagnosis.

Technologies

Beckhoff TwinCAT 3 Structured Text PRECIA EtherNet/IP PROFIBUS DeviceNet Modbus TCP

My contribution

  • I configured and tested communication with I410/I410G equipment and integrated the I400G DSD through DeviceNet.
  • I also worked with PROFIBUS for weighing data. For EtherNet/IP and DeviceNet, I mapped the data and adapted the decoding to handle signed weight values.
  • I diagnosed communication and made data available through Modbus TCP according to the destination system.
  • I prepared configuration, wiring and implementation documents.
  • On setups with the I410G, I used its display as my reference. I compared the weight shown there with the value received by the PLC or displayed in Dorner, depending on the setup.

Approach and technical considerations

  • Retain the existing byte-by-byte data organization in the DeviceNet programme.
  • Work on a combined EtherNet/IP/DeviceNet configuration with protocol selection and support for one to four scales.
  • Retain configuration parameters after a power interruption.

Work carried out

  • Equipment communication configurations, mappings and decoding adaptations.
  • A combined protocol configuration and implementation documentation.

Observed results

  • Communications and configurations were validated on the setups that were tested.

Limits of this work

  • Validation applies to those setups, not universal compatibility or generalized production deployment.
  • The work does not establish metrological certification. Device and protocol combinations require adaptation.